RevA MN300282 7of34
GETTINGSTARTED(continued) StepFour
TOP‐LEVELMENUDescriptions
UNITS–Allowsendusertoselecttheunitsforconfigurationandoperation.
o Select between Inches, Centimeters, Feet, Meters or
Percent.
o PressEXITtoreturntotheTOP‐LEVELMENU.
TANK–Allowstheendusertoconfiguretheoperationalrange
fortheswitchaswellasthe4‐20mAoutputsignal.
o HEIGHT – Distance from the transducer face to the
bottomofthetank.
o FILL‐H – Maximum fill height of the liquid from the
bottomofthetank.
o Note: The 4 and 20 mA points are set by settingthese
twopoints.
The 20 mA point is at the Fill‐H and the 4 mA
pointisatthebottomofthetank.
The4and20mAsetpointscannotbereversed.
o PressExittoreturntotheTOP‐LEVELMENU
o Note:ifUNITSissettoPercent,thenTANKwillnotappear.ToviewTANK,setUNITStoanyofthe
following:Inches,Centimeters,FeetorMeters
RELAY 1, RELAY 2 or RELAY 3 – Allows end user to configure the function and operation of each relay.
Each relay has a small black circle that appears when the relay is energized.When the relay is de‐
energized,theblackcircledisappears.
o PUMP – Pump operation allows for two separate level set points (Relay ON and Relay OFF).
ChoosebetweentheEMPTYorFILLoperation.Bothoperationsrequiresetting alevelforONand
anotherlevelforOFF
EMPTY–usedtocontrolapumpthatemptiesatank.
Typically,RelayONistheHIGHsetpointandRelayOFFtheLOWsetpoint.Relaywill
energizeatthehighsetpoint(ON)andremainonuntilthelevel
reachesthelowset
point(OFF).Itwillremainoffuntilthelevelreturnstothehighsetpoint(ON).