GETTINGSTARTED(continued) StepFour
TOPLEVELMENUDescriptions
UNITSAllowsendusertoselecttheunitsforconfigurationandoperation.
o Select between Inches, Centimeters, Feet, Meters or
Percent.
o PressEXITtoreturntotheTOPLEVELMENU.
TANKAllowstheendusertoconfiguretheoperationalrange
fortheswitchaswellasthe420mAoutputsignal.
o HEIGHT Distance from the transducer face to the
bottomofthetank.
o FILLH Maximum fill height of the liquid from the
bottomofthetank.
o Note: The 4 and 20 mA points are set by settingthese
twopoints.
The 20 mA point is at the FillH and the 4 mA
pointisatthebottomofthetank.
The4and20mAsetpointscannotbereversed.
o PressExittoreturntotheTOPLEVELMENU
o Note:ifUNITSissettoPercent,thenTANKwillnotappear.ToviewTANK,setUNITStoanyofthe
following:Inches,Centimeters,FeetorMeters
RELAY 1, RELAY 2 or RELAY 3 Allows end user to configure the function and operation of each relay.
Each relay has a small black circle that appears when the relay is energized.When the relay is de
energized,theblackcircledisappears.
o PUMP Pump operation allows for two separate level set points (Relay ON and Relay OFF).
ChoosebetweentheEMPTYorFILLoperation.Bothoperationsrequiresetting alevelforONand
anotherlevelforOFF
EMPTYusedtocontrolapumpthatemptiesatank.
Typically,RelayONistheHIGHsetpointandRelayOFFtheLOWsetpoint.Relaywill
energizeatthehighsetpoint(ON)andremainonuntilthelevel
reachesthelowset
point(OFF).Itwillremainoffuntilthelevelreturnstothehighsetpoint(ON).
