27 AUG 08 PRELIMINARY MANUAL 21 of 57
Rev 1_3 Commander LI90 Series
Application #1
• Overview
o Multi-Tank Display – The LI90 series in this application is typically used to
eliminate the need of one display for each transmitter. This application can accept
up to Four 4-20 mA input transmitters and will provide a 3A SPST relay output
for each input.
• Power: Operate from 12 to 24 VDC power
• Inputs: Accept up to four 4-20 mA inputs, the inputs will be powered by
12 to 24 VDC power source
• Outputs: Each input channel has a relay assigned (4 relays total)
• Mounting: Commander can be ¼ DIN mounted and DIN rail mountable